Firetech 8-Zones Conventional Fire Alarm control Panel(FT-CFP2002-8)

Description:

1 The Firetech FT-CFP2002-8 series 8-Zones conventional fire alarm panel is designed based on EN54 part 2&4 standard.

 2 It is modularized design, the panel can expend from 1 zone to 32 zones easily

 3 It has 2 level control mode by a lock

 4 It has 24VDC and 5VDC power supply output.

 5 It has FIRE and FAULT signal output.

 6 It has 2 general sounders output.

 7 Each zone has 1 circuit detectors input .

 8 Each zone can be disable by a button.

 9 It has RESET button to reset the panel.

 10 It has SILENCE button to stop BUZZER and SOUNDERS.

 11 It has EVACUATE button to start a manual fire alarm immediately.

 12 It has battery low protection function, when battery voltage lower than 21VDC, 

     battery will be cut off automatically until the mains power is on.

 13 It has an optional GSM module for fire alarm by SMS .

 14 It is economic, user-friendly and easy maintenance.

Parameters:
ITEM 8 Zone panel
Model No. FT-CFP2002-8

Power specification
 


Mains supply voltage 110VAC or 240VAC

Internal power supply 27.2VDC

Total output current limited 500mA @ 240VAC

Main supply monitor for fault Yes

Battery protection for low voltage Yes

Batteries (default configuration) 12V2AH*2

Detector circuit specification
 


Number of circuit 8


Line fault monitor for open circuit Yes

Line fault monitor for short circuit Yes

Line fault monitor for detector removal Yes, if End of Line Monitor Unit fitted in place of End of Line Resistor

End of Line device 6.8k Ω,5% tolerance, 0.25W (colour code-blue,grey,red,gold)

Detector continuity diodes Silicon 1N4001 or Schottky type (required if End of Line Monitor Unit fitted to give Detector Removal Fault)

Call point resistor value 470 to 680 Ω, 0.225 or 0.5 watt

Maximum number of smoke/heat detectors per zone 20 (based on a total detector current of 2mA, each detector consuming 100μA).Note: if End of Line Monitor Unit is fitted,
for correct operation maxmum voltage drop must not exceed 12 volts.


Maximum number of manual call points per zone No limit

Sounder circuit specification
 


Number of general circuits 8


End of line resistor value 6.8k Ω,5% tolerance, 0.25W (colour code-blue,grey,red,gold)

Line fault monitor for open circuit Yes

Line fault monitor for short circuit Yes

Outputs fused AT 400mA

Maximum number of bells @ 20mA of each sounder output 20

Fuses
 


Battery fuse 1.5A F 20mm

Sounder outputs 500mA F 20mm

Fire and fault output
 


Output type NC and NO relay

Maximum current 100mA

Connection block
 


Largest acceptable conductor size 2.5mm2

Smallest acceptable conductor size 0.75mm2

Size and weight
 
 


Dimensions(mm) 395*502*125mm

Weight (without batteries) 7kg

Weight (with batteries) 10.5kg